GB 50261-2017 第8.0.8条 Code for construction and acceptance of sprinkler systems

System Acceptance消防工程

GB 50261-2017 第8.0.8条

| | During acceptance, the system piping network's hydrostatic strength test, tightness test records and flushing records shall be checked, and the test pressure, duration and results shall be verified. |