GB 50261-2017 第6.2.4条 Code for construction and acceptance of automatic sprinkler systems

System commissioning消防工程

GB 50261-2017 第6.2.4条

| **** | Drain water at the end-of-line test valve; the system should start the fire pump within the specified time (within 1 min) and feed back the water flow indicator and pressure switch signals. |