GB 50261-2017 第6.2.2条 Code for construction and acceptance of sprinkler systems

System commissioning消防工程

GB 50261-2017 第6.2.2条

| **** | The start/stop pressure of the jockey pump shall comply with the design requirements, and the number of start/stop cycles shall not exceed 15 times/h. |