GB 50261-2017 第5.5.1条 Code for construction and acceptance of sprinkler systems

Construction消防工程

GB 50261-2017 第5.5.1条

| **** | Check valves, control valves and pressure gauges shall be installed on the discharge pipes of fire pumps; control valves and pressure gauges shall be installed on the suction pipes of fire pumps, and strainers should be installed. |