GB 50034-2013 第7.2.3条 Architectural Lighting Design Standard

Lighting power distribution and control电气工程

GB 50034-2013 第7.2.3条

| **** | The current of each single-phase lighting branch circuit should not exceed 16A, and the number of connected light sources or LED luminaires should not exceed 25. For large combined architectural luminaires, each circuit should not exceed 25A, and the number of light sources should not exceed 60. |