ME HotelM&E AI
Home › Standards › GB 50057-2010 › 第4.3.5条

GB 50057-2010 第4.3.5条 Code for Design Protection of Structures Against Lightning

Down conductor电气工程

GB 50057-2010 第4.3.5条

| **** | **When using building reinforcement as down conductors, if the rebar diameter is ≥16 mm, 2 rebars (tied or welded) shall be used as one group of down conductors; if the rebar diameter is 10 mm–16 mm, 4 rebars (tied or welded) shall be used as one group of down conductors.** |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.