GB 50016-2014 (2018年版) 第8.4.1条 Code for Fire Protection Design of Buildings

Smoke control and smoke exhaust消防工程

GB 50016-2014 (2018年版) 第8.4.1条

| The following buildings or locations shall be provided with smoke exhaust facilities: song-and-dance entertainment, screening and amusement venues located on the first, second or third floor with a room floor area greater than 100 m²; atriums; above-ground rooms in public buildings with a floor area greater than 100 m² that are regularly occupied; above-ground rooms in public buildings with a floor area greater than 300 m² containing large amounts of combustibles; escape corridors in buildings longer than 20 m (applicable to hotel buildings). |