GB 50116-2013 第3.4.1条 Code for Design of Automatic Fire Alarm Systems

System Equipment消防工程

GB 50116-2013 第3.4.1条

| Fire control room provision: A separately constructed fire control room shall have a fire resistance rating not lower than Grade II; when incorporated within a building, it should preferably be located on the ground floor or the basement level adjacent to an exterior wall, and a safe exit leading directly outdoors shall be provided.