GB 50116-2013 第2.0.6条
| The fire control room shall be equipped with devices for fire alarm, fire linkage control and fire emergency broadcasting; it shall be located on the ground floor or the basement level 1 of the building, and its evacuation door shall open directly to the outdoors or to a safe exit.