GB 50116-2013 第3.2.1条 Code for Design of Automatic Fire Alarm Systems

System equipment消防工程

GB 50116-2013 第3.2.1条

| Fire alarm control panel capacity: The total number of devices and total number of addresses connected to each control panel shall not exceed 3200 points, of which the number of devices connected to each bus circuit should not exceed 200 points, and a margin of not less than 10% of the rated capacity shall be reserved.