GB 50116-2013 第3.1.6条 Code for Design of Automatic Fire Alarm Systems

System design消防工程

GB 50116-2013 第3.1.6条

| Bus short-circuit isolators shall be provided on the system bus, and the total number of fire protection devices such as fire detectors, manual fire alarm call points and modules protected by each bus short-circuit isolator shall not exceed 32 points; where the bus crosses a fire compartment, a bus short-circuit isolator shall be provided at the crossing point.