GB 50736-2012 第8.3.1条 Code for Design of Heating, Ventilation and Air Conditioning of Civil Buildings

Sound attenuation and vibration isolation暖通空调

GB 50736-2012 第8.3.1条

| Air velocity in air ducts of the air-conditioning system shall comply with the following requirements: the air velocity in the main duct should not exceed 8 m/s, and that in branch ducts should not exceed 5 m/s; for quiet rooms such as guest rooms in hotel buildings, the air velocity in the main duct should not exceed 5 m/s, and that in branch ducts should not exceed 3 m/s.