GB 50736-2012 第2.0.8条 Code for Design of Heating, Ventilation and Air Conditioning of Civil Buildings

Terminology暖通空调

GB 50736-2012 第2.0.8条

| Ventilation system outdoor air volume: The minimum outdoor air volume for hotel guest rooms shall not be less than 30 m³/(h·person) (defined in the terminology chapter, applicable to hotel buildings).