During the commissioning of the hotel's cooling plant (centrifugal chillers), surging occurs frequently. How should this be systematically analyzed and addressed?

Expert Q&APaul Qiao · MEP DirectorUpdated 2026-05-04
P
Paul Qiao
MEP Director

During the commissioning of the hotel's cooling plant (centrifugal chillers), surging occurs frequently. How should this be systematically analyzed and addressed?

Centrifugal chiller surging is one of the most intractable problems in hotel MEP commissioning, involving a multidisciplinary intersection of thermodynamics, fluid mechanics, control theory and engineering practice experience. The following is an in-depth analysis for hotel projects.

I. Standard and Code References
"Centrifugal Water Chillers" (GB/T 18430.1-2020) specifies the design, manufacturing and performance testing requirements for water chillers, in which Clause 5.4.3 states that units should operate stably under specified conditions without surging. "Code for Construction and Acceptance of Refrigeration Equipment Installation Engineering" (GB 50274-2010) Clause 4.2.7 requires that during trial operation of equipment, the suction and discharge pressures and temperatures of the compressor be checked to be within the design range. "Design Standard for Energy Efficiency of Public Buildings" (GB 50189-2015) Clause 4.2.6 sets specific requirements for chiller energy efficiency values (COP, IPLV), indirectly constraining unit selection and load matching. ASHRAE Guideline 22-2012 "Chiller Plant Design and Construction" has a dedicated chapter on surge control for centrifugal machines.

II. Impact on Hotel Operations (Pros and Cons)
Pros: Once the surging problem is successfully resolved, the unit's operating efficiency (COP value) will reach the design maximum; the full-load COP of a centrifugal machine can reach 6.0-7.0 (screw machines 5.0-6.0), yielding significant electricity savings. For a 50,000 m² five-star hotel, the cooling season (6 months) electricity cost is approximately 1.5-2.5 million RMB, and high-efficiency chillers can save 15-25% of electricity costs.
Cons: Surging not only fails to provide cooling but also causes severe mechanical damage—during surging, the violent fluctuation of impeller axial force leads to thrust bearing wear or even fracture, with bearing replacement costs of approximately 50,000-150,000 RMB; the high-frequency vibration induced by surging may cause refrigerant pipe rupture and heat exchange tube cracking (Carrier 19XR series has had actual cases where, after the impeller shattered, fragments entered the condenser and scrapped a heat exchange tube bundle worth 200,000 RMB); the noise during surging reaches as high as 100-120 dB, seriously affecting hotel guest experience and the staff working environment (normal compressor operating noise is 78-85 dB). Once surging occurs during the operating period, the cooling supply is interrupted, rendering guest rooms, banquet halls and restaurants unusable, with direct economic losses of tens of thousands of RMB per hour.

III. Pros and Cons of Later Maintenance
Pros: The surge commissioning process is in fact a comprehensive system inspection—cooling water quality, condenser cleanliness, refrigerant purity and control system parameters are all corrected to the optimal state, laying a foundation for subsequent safe operation. The commissioning data serves as the baseline of the unit's "health record," and subsequent maintenance comparison analysis can provide early warning of potential problems.
Cons: The damage caused by surging to mechanical components is cumulative. Even if surging is temporarily eliminated after commissioning, micro-cracks in the impeller and diffuser, the fatigue life of bearings and the wear of seals have already begun to accumulate. During the operating period, the frequency of preventive maintenance needs to be increased—bearing vibration monitoring from once per quarter to once per month, and refrigerant composition analysis from once per year to once every six months.

IV. Cost Pros and Cons
Short-term costs: The investment in surge commissioning includes: commissioning engineer (OEM service) cost of approximately 3,000-5,000 RMB/day, with a commissioning period of 3-7 days; if a hot gas bypass pipe needs to be added, material + installation cost of approximately 30,000-80,000 RMB (including refrigerant recovery and recharge cost of 5,000-10,000 RMB); possibly adding cooling tower fan VFDs and a cooling water bypass valve (investment of 50,000-150,000 RMB).
Long-term benefits: After successfully eliminating surging, the unit's service life can be extended by 5-8 years (design life 20-25 years), and the cooling-season electricity cost is reduced by approximately 15-25% each year. If the compressor is scrapped due to surging, the cost of replacing a centrifugal compressor is approximately 40-60% of the whole-machine cost (compressor price for 300-800 kW models is 150,000-400,000 RMB), plus installation and commissioning costs, for a total investment of 500,000-800,000 RMB. The upfront investment clearly has a very high cost-effectiveness.

V. Specific Technical Details and Engineering Experience
1) Actual method for determining the surge line: During commissioning, gradually close the guide vane opening (reducing by 5% each time) while monitoring the compressor discharge pressure and suction pressure difference (i.e., pressure ratio), record the guide vane opening and pressure ratio at which surging occurs, and plot the actual surge line. Shift the surge line downward by 5-10% (i.e., leaving a safety margin) and write it into the controller. This operation requires VFD support for low-speed operation (30-40% speed) in coordination, and the entire commissioning takes approximately 4-6 hours.
2) Key parameter indicators for cooling water side commissioning: The cooling water supply-return temperature difference should be between 4-6℃ (design value 5℃), and the condenser approach (condensing temperature - cooling water leaving temperature) corresponding to minimum flow should be ≤2.5℃. If the approach exceeds 3.5℃, it indicates severe fouling or blockage of the condenser heat exchange tubes or impure refrigerant. For every 1℃ rise in approach, the unit COP drops by approximately 2-3%.
3) Design parameters of the hot gas bypass pipe: The pipe diameter is generally 1/4-1/3 of the main unit's suction pipe diameter, taken from the compressor discharge pipe (before the condenser inlet) and connected to the evaporator inlet (before the compressor suction inlet), with an electric regulating valve and silencer installed on the pipeline. The hot gas bypass volume should not exceed 10-15% of the compressor discharge volume (otherwise excessive hot gas entering the evaporator will reduce cooling effect). During bypass pipe installation, a refrigerant filter and oil return bends must be provided (lower oil return bend height ≥200 mm).
4) Commissioning experience data: An InterContinental hotel project used 3 York YK series centrifugal machines (single unit cooling capacity 1200 RT). During commissioning, it was found that Unit No. 1 surged at 30-50% load. Inspection revealed that the cooling tower leaving water temperature was only 22℃ (10℃ lower than the design 32℃), and the excessively low condensing pressure prevented the oil pressure differential from being established. The solution was to shut off some cooling tower fans and adjust the cooling water bypass valve opening to control the cooling water leaving temperature at 26-28℃. After adjustment, surging disappeared and the unit COP increased from 4.8 to 6.2.
5) Oil circuit system inspection: The centrifugal machine oil pressure differential (oil pump outlet pressure - compressor suction pressure) should be maintained at 150-200 kPa. During surging, the sharp fluctuation of oil pressure differential may trigger the "low oil pressure shutdown" protection. Before commissioning, confirm that the oil heater has been running continuously for more than 24 hours (to ensure complete separation of refrigerant from the lubricating oil), and the oil filter pressure differential is ≤35 kPa.
6) Differences in surge commissioning characteristics among brands: Carrier 19XR guide vanes have a slow response speed (full stroke 15-20 seconds), and surging mostly occurs under rapid guide vane closing conditions; the solution is to reduce the guide vane closing rate to 50% of the original value. York YK guide vanes have a fast response (full stroke 8-12 seconds), and surging mostly occurs under excessively high condensing pressure conditions, with the focus on cooling tower side issues. Trane CenTraVac adopts three-stage compression, with an economizer between the low-pressure stage and high-pressure stage; surging is relatively less frequent but once it occurs it is more complex to handle (the two stages of guide vanes need to be adjusted separately).

VI. Preventive Design Measures for Surge
Multiple measures can be taken at the design stage to prevent surge: ① When selecting chillers, note that the capacity of a single unit should not be too large—it is recommended that the cooling capacity of a single unit not exceed 1200RT (for a five-star hotel, typically 2–3 units of 500–800RT are more conducive to part-load operation and surge control than a single 2000RT unit); ② Give priority to units with a "hot gas bypass" function (some brands, such as the Trane CVHG series, are equipped with hot gas bypass as standard, which can bypass part of the hot gas to the evaporator at low load to raise the evaporating pressure and prevent surge); ③ The design temperature difference of the cooling water system shall strictly be 5℃, and the cooling tower selection should have a margin (the selection heat load shall be 1.2 times the condenser load of the chiller, and the cooling water temperature rise shall be designed at 5℃); ④ When the chilled water system adopts a "primary pump variable flow" system, a "minimum flow bypass pipe" shall be installed between the chilled water supply and return headers to ensure that the flow of a single unit at low load is not lower than the minimum allowable value.

VII. Surge Accident Case and Lessons
A Hilton hotel project used 3 York YK series centrifugal chillers (1200RT each). During commissioning, Unit No. 3 experienced severe surge at 40% load, accompanied by metallic impact noise (bearing fracture). Post-incident disassembly analysis found that the babbitt layer of the compressor thrust bearing had completely detached, and there was slight scraping between the impeller and the diffuser. The direct cause was that the cooling tower was not restored after winter maintenance (the cooling tower wind deflectors had been removed, and the cooling water inlet temperature dropped to 18℃, resulting in excessively low condensing pressure), while the surge protection logic of the unit controller was not enabled (the manufacturer's default setting was off and required manual activation). Repair costs: replacement of the thrust bearing assembly (including seals) approximately RMB 32,000, re-calibration of impeller dynamic balance approximately RMB 18,000, refrigerant recovery and recharge approximately RMB 15,000, labor approximately RMB 20,000, totaling approximately RMB 85,000. Downtime was 7 days, during which hotel banquet booking was affected (estimated loss of approximately RMB 500,000). Lessons: ① Before unit commissioning, the status of the cooling tower and cooling water system must be comprehensively checked; ② All safety protection logic must be enabled and tested (surge protection, low evaporating temperature protection, oil pressure differential protection); ③ Establish a "unit commissioning checklist" and have it double-signed and confirmed by the manufacturer and the installation contractor.

VIII. Surge Warning and Remote Diagnostic System
With the development of IoT technology, surge warning has become possible. Install online vibration monitoring sensors (accelerometers; installation locations: bearing housing in X/Y/Z three directions, motor shaft extension end bearing housing) on centrifugal chillers, and combine them with the unit's built-in temperature sensors (discharge temperature, condensing temperature, evaporating temperature) and pressure sensors (discharge pressure, suction pressure, oil pressure) to build a surge warning model. When the monitored pressure ratio of discharge pressure to suction pressure approaches the surge line (deviation <5%) and the vibration amplitude increases by >30% within 10 seconds, the system automatically issues a warning signal and notifies O&M personnel through the BA system. The warning lead time can reach 10–30 minutes, during which O&M personnel can avoid surge by adjusting the guide vane opening, increasing cooling water flow, or raising the cooling water outlet temperature. The remote diagnostic system can also upload operating data to a cloud platform (such as Johnson Controls' OpenBlue or Siemens' Desigo CC), where analysis engineers at the manufacturer's data center perform remote fault diagnosis, enabling the transition from "preventive maintenance" to "predictive maintenance."

Standard reference

GB/T 18430.1-2020GB 50274-2010GB 50189-2015