Expert Q&APaul Qiao · MEP DirectorUpdated 2026-07-13
P
Paul Qiao
MEP Director

What size cable should be used for a 2500KVA transformer?

Your question is highly critical and directly relates to the safety and cost-effectiveness of the hotel's power supply system. As MEP Director, I need to provide you with a professional, actionable solution from a holistic perspective, integrating standards, load characteristics, construction techniques, and operational convenience.

First, I must clearly state: The total capacity of "2500kVA" is a signal that requires careful handling for a hotel project. According to GB 50053-2013 *Code for Design of 20kV and Below Substations* Clause 3.3.2 and GB 50052-2009 *Code for Design of Power Supply and Distribution Systems* Clause 6.0.5, the capacity of a single transformer should not exceed 1250kVA. Therefore, 2500kVA is almost impossible to be carried by a single transformer, typically implying a configuration of two 1250kVA transformers or two 1600kVA transformers. Cable specification selection must be based on this actual configuration and the voltage level on the high-voltage side.

Regarding your core question, I will provide a detailed analysis based on the two most likely high-voltage supply schemes:

Scheme 1: 10kV High-Voltage Supply (Most Common Scheme)

This is the most mainstream choice for hotel projects, applicable to projects with total electrical capacity within 10MVA.

1. Load Rate and Economic Operation:

2. Cable Specification Selection:

Scheme 2: 35kV High-Voltage Supply (Special Case)

This scheme is only considered when the hotel's total electrical capacity approaches or exceeds 10MVA and the municipal grid has 35kV connection conditions. For example, a large resort hotel with over 800 guest rooms or a comprehensive hotel incorporating a large convention and exhibition center.

1. Capacity and Current: Assuming a total capacity of 2500kVA with 35kV supply, the rated current is approximately: I = 2500 / (1.732 * 35) ≈ 41A.

2. Cable Specification Selection:

Director-Level Decision Points and Lessons Learned

1. Capacity Decomposition is the First Priority: When you hear "2500kVA transformer," the first thing to do is verify and decompose. Directly confirm with the design institute or electrical consultant: "Is it a single 2500kVA unit, or two 1250kVA units?" A single 2500kVA unit is almost infeasible in hotel projects—it not only violates codes but also results in enormous low-voltage short-circuit currents, making switchgear selection difficult and costs surge.

2. High-Voltage Supply Scheme Comparison: As mentioned above, an economic comparison between 10kV and 35kV must be conducted based on total electrical capacity and municipal grid conditions. This requires early communication with the local power supply bureau to clarify the supply scheme approval. As Director, you need to lead this decision to avoid the design institute defaulting to 10kV, which could lead to a passive situation later due to capacity exceeding limits.

3. Cable Selection Must Consider Full Lifecycle Cost: Do not focus solely on initial investment. Choosing a slightly larger cable cross-section (e.g., 95mm² vs. 70mm²), although increasing initial cost by a few thousand yuan, can significantly reduce line loss over the future 20-30 year operational period and avoid the high cost of cable modification for future capacity expansion. This is a key decision that embodies the concept of "full lifecycle management."

4. Key Construction and Acceptance Points:

Final Recommendation:

For the 2500kVA capacity you mentioned, I recommend you first confirm whether it is a 10kV supply scheme with two 1250kVA transformers. On that premise, the incoming cables are recommended to be YJV-8.7/15kV 3×95mm² copper-core power cables. This scheme achieves the optimal balance among safety, economy, construction convenience and future adaptability, and meets the director-level management goals of hotel MEP engineering: "safe and reliable, economical and applicable, green and energy-saving, efficient operation and maintenance."

Standard reference

GB 50053-2013GB 50052-2009GB/T 13462-2008GB 50217-2018GB 50217-2018.