GB 50736-2012 第6.1.3条 Design Code for Heating, Ventilation and Air Conditioning of Civil Buildings

Ventilation暖通空调

GB 50736-2012 第6.1.3条

| The bottom of the outdoor air intake of a mechanical supply air system should be no less than 2 m above the outdoor ground, and no less than 1 m when located in a landscaped area; the exhaust air outlet should be higher than the intake, with a vertical distance of no less than 6 m and a horizontal distance of no less than 3 m.