ME HotelM&E AI
Home › Standards › GB 50222-2017 › 第4.0.9条

GB 50222-2017 第4.0.9条 Code for Fire Protection Design of Building Interior Decoration

Civil buildings消防工程

GB 50222-2017 第4.0.9条

| | When song-and-dance entertainment and amusement venues (such as KTVs, dance halls, etc.) in hotel buildings are located in buildings of fire resistance rating Class I or II, their ceiling finish materials shall be Class A, and other parts (walls, floors, partitions, fixed furniture, etc.) shall not be lower than Class B1; when located in buildings of fire resistance rating Class III, ceilings and walls shall be Class A, and other parts shall not be lower than Class B1. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →