ME HotelM&E AI
Home › Standards › GB 50034-2013 › 第5.2.1条

GB 50034-2013 第5.2.1条 Architectural Lighting Design Standard

Lighting quantity and quality电气工程

GB 50034-2013 第5.2.1条

| **** | **Hotel building lighting standard values (Table 5.2.1):** <br>- **Guest room**: General activity area 75 lx, bedside reading 150 lx (0.75 m horizontal plane), writing desk 300 lx, bathroom 150 lx (0.75 m horizontal plane).<br>- **Restaurant/Banquet hall**: 300 lx (0.75 m horizontal plane), UGR≤22, Ra≥80.<br>- **Multifunction hall**: 300 lx (0.75 m horizontal plane), UGR≤22, Ra≥80.<br>- **Lobby/Reception desk**: 300 lx (floor), UGR≤22, Ra≥80.<br>- **Corridor/Stairwell**: 50 lx (floor), UGR≤25, Ra≥60.<br>- **Meeting room**: 300 lx (0.75 m horizontal plane), UGR≤19, Ra≥80.<br>- **Fitness/Recreation room**: 200 lx (0.75 m horizontal plane), UGR≤22, Ra≥80.<br>- **Kitchen**: 200 lx (0.75 m horizontal plane), UGR≤25, Ra≥80.<br>- **Laundry room**: 200 lx (0.75 m horizontal plane), UGR≤25, Ra≥60.<br>- **Storage room**: 100 lx (floor), UGR≤25, Ra≥60.

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.