GB 50057-2010 第6.4.2条 Code for Design Protection of Structures Against Lightning

Lightning electromagnetic pulse电气工程

GB 50057-2010 第6.4.2条

| | Weak-current wiring in the hotel (such as structured cabling) shall be installed in metal conduits or metal cable trays; both ends of the metal conduit shall be equipotentially bonded, and the spacing between connection points to the grounding grid should not exceed 15 m. |