ME HotelM&E AI
Home › Standards › GB 50057-2010 › 第6.4.1条

GB 50057-2010 第6.4.1条 Code for Design Protection of Structures Against Lightning

Lightning electromagnetic pulse电气工程

GB 50057-2010 第6.4.1条

| | The shielding of electronic information system equipment rooms in hotel buildings shall comply with the following requirements: the shielding mesh size of the equipment room should not be greater than 2m×2m, and the shielding effectiveness shall not be less than 20dB (within the frequency range of 1MHz~1GHz). |