ME HotelM&E AI
Home › Standards › GB 50057-2010 › 第6.3.5条

GB 50057-2010 第6.3.5条 Code for Design Protection of Structures Against Lightning

Equipotential bonding电气工程

GB 50057-2010 第6.3.5条

| Equipotential bonding for the swimming pool and SPA area (if any) within the hotel: all metal components (such as metal ladders, metal luminaire enclosures, metal pipes, metal grilles) shall be connected to the equipotential bonding bar, with a connecting conductor cross-sectional area of not less than 16 mm² copper. The grounding resistance of the equipotential bonding bar in this area shall not exceed 1 Ω.

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.