ME HotelM&E AI
Home › Standards › GB 50057-2010 › 第5.2.4条

GB 50057-2010 第5.2.4条 Code for Design Protection of Structures Against Lightning

Down conductor电气工程

GB 50057-2010 第5.2.4条

| **** | **(Grounding system) Lightning protection grounding, electrical equipment grounding, and information system grounding should share a common grounding system, with a grounding resistance not exceeding 1Ω. When a common grounding system is used, a main equipotential bonding terminal board should be installed at each down-conductor location.** |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.