GB 50057-2010 第4.4.3条
| **** | **(For Class III lightning protection buildings) There shall be no fewer than 2 dedicated down conductors, arranged evenly and symmetrically around the perimeter of the building and around the inner courtyard, with spacing calculated along the perimeter not exceeding 25 m.** |