ME HotelM&E AI
Home › Standards › GB 50057-2010 › 第5.2.5条

GB 50057-2010 第5.2.5条 Code for Design Protection of Structures Against Lightning

Air termination电气工程

GB 50057-2010 第5.2.5条

**** | Air-termination network mesh size requirements: For Class II lightning protection buildings (a common category for hotels), the mesh size shall not exceed **10m×10m** or **12m×8m**; for Class III lightning protection buildings, the mesh size shall not exceed **20m×20m** or **24m×16m**.