GB 50057-2010 第5.2.4条
**** | Air termination strips should be installed on parts of the building susceptible to lightning strikes (such as roof corners, ridges, eaves, parapets, etc.). When round steel is used, the diameter should not be less than **8mm**; when flat steel is used, the cross-section should not be less than **48mm²**, and the thickness should not be less than **4mm**.