ME HotelM&E AI
Home › Standards › GB 50057-2010 › 第4.5.1条

GB 50057-2010 第4.5.1条 Code for Design Protection of Structures Against Lightning

Lightning protection device电气工程

GB 50057-2010 第4.5.1条

| **** | **Side-flash lightning protection**: For a Class II lightning protection hotel building exceeding **30m** in height, a horizontal air-termination conductor shall be installed around the building perimeter at every floor starting from **30m**, with structural ring beam reinforcement used as the equipotential ring. For a Class III lightning protection hotel building exceeding **60m** in height, installation shall start from **60m**. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.