GB 50057-2010 第0.05条 Code for Design Protection of Structures Against Lightning

Classification of lightning protection for buildings电气工程

GB 50057-2010 第0.05条

**Note**: The specific lightning protection classification of a hotel building shall be determined based on its importance, occupant density and expected lightning strike frequency (N). The calculation method for the expected lightning strike frequency N is given in Appendix A of the standard, involving parameters such as local thunderstorm days and the equivalent area of the building. Generally, if a hotel is a densely occupied public building, it is classified as Class II when N > times/a; as Class III when 0.01 ≤ N ≤ 0.05 times/a; if treated as an ordinary civil building, it is classified as Class II when N > 0.25 times/a, and as Class III when 0.05 ≤ N ≤ 0.25 times/a.

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.