GB 50116-2013 第11.1.6条
| Automatic fire alarm system wiring shall not be installed in the same conduit or trunking as other wiring (such as lighting, power, low-voltage systems, etc.). Where shared trunking is unavoidable, metal dividers shall be provided for separation, with a spacing of not less than 100 mm.