ME HotelM&E AI
Home › Standards › GB 50116-2013 › 第11.1.1条

GB 50116-2013 第11.1.1条 Code for Design of Automatic Fire Alarm Systems

Cabling消防工程

GB 50116-2013 第11.1.1条

| Transmission lines of the automatic fire alarm system and control lines powered at below 50V shall use copper-core insulated conductors or copper-core cables with a voltage rating of not less than AC 300/500V. Power supply and control lines using AC 220/380V shall use copper-core insulated conductors or copper-core cables with a voltage rating of not less than AC 450/750V. |