GB 50116-2013 第10.1.4条 Code for Design of Automatic Fire Alarm Systems

System power supply消防工程

GB 50116-2013 第10.1.4条

| The main power supply of the automatic fire alarm system shall not be provided with residual current-operated protection or overload protection devices (unless the protection device only triggers an alarm without cutting off the power supply).