GB 50116-2013 第4.10.1条 Code for design of automatic fire alarm systems

Fire alarm linkage control消防工程

GB 50116-2013 第4.10.1条

| | The fire linkage controller shall have the function of cutting off non-fire power supplies in the fire area and related areas. When normal lighting needs to be cut off, it should preferably be cut off before the automatic sprinkler system and fire hydrant system operate. |