ME HotelM&E AI
Home › Standards › GB 50116-2013 › 第4.8.1条

GB 50116-2013 第4.8.1条 Code for Design of Automatic Fire Alarm Systems

Fire alarm linkage control消防工程

GB 50116-2013 第4.8.1条

| | Linkage control of the fire emergency lighting and evacuation indication system: it shall be implemented by the fire alarm control panel or the fire linkage controller starting the emergency lighting controller; all non-maintained lighting luminaires in the system shall be fully illuminated, and maintained luminaires shall switch to the emergency operating state. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.