GB 50116-2013 第4.5.2条
| | Linkage control of the smoke exhaust system: the alarm signal from two independent fire detectors in the same smoke control zone, or the alarm signal from one fire detector and one manual fire alarm call point, shall serve as the linkage trigger signal for opening the smoke exhaust outlet, smoke exhaust window or smoke exhaust valve. |