GB 50116-2013 第4.2.2条
| | Linked control of the pre-action system: the alarm signals from two or more independent smoke fire detectors in the same alarm zone, or from one smoke fire detector and one manual fire alarm call point, shall serve as the linked trigger signal for opening the pre-action valve assembly. |