ME HotelM&E AI
Home › Standards › GB 50116-2013 › 第5.2.8条

GB 50116-2013 第5.2.8条 Code for Design of Automatic Fire Alarm Systems

Fire detector消防工程

GB 50116-2013 第5.2.8条

| The horizontal distance from the detector to walls and beam edges shall not be less than 0.5 m; the horizontal distance to the edge of an air-conditioning supply outlet shall not be less than 1.5 m, and the detector should preferably be installed close to a return air inlet. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.