GB 50116-2013 第5.2.7条 Code for design of automatic fire alarm systems

Fire detector消防工程

GB 50116-2013 第5.2.7条

| When a room is partitioned by bookshelves, equipment, partitions, etc., and the distance from their top to the ceiling or beam is less than 5% of the room's clear height, at least one detector shall be installed in each partitioned section.