GB 50116-2013 第6.6.1条 Code for design of automatic fire alarm systems

System Equipment消防工程

GB 50116-2013 第6.6.1条

| Fire emergency broadcasting: Fire emergency broadcast speakers should be installed in hotel guest rooms, corridors and other areas; the speaker power should not be less than 3W, and the walking distance from any location within a fire compartment to the nearest speaker should not exceed 25m.