GB 50016-2014 (2018年版) 第8.3.3条
| Unless otherwise specified in the code, the following buildings shall be provided with automatic fire extinguishing systems (including automatic sprinkler systems): Class I high-rise public buildings (including hotels) and their basements and semi-basements; residential buildings with a building height greater than 100 m; the sprinkler discharge density of the automatic sprinkler system shall not be less than 6 L/min·m² (Medium Hazard Class I), and the area of operation shall not be less than 160 m².