GB 50116-2013 第6.3.1条 Code for Design of Automatic Fire Alarm Systems

System equipment消防工程

GB 50116-2013 第6.3.1条

| Manual fire alarm call point: at least 1 unit shall be provided in each fire compartment; the walking distance from any location within a fire compartment to the nearest manual call point shall not exceed 30 m.