GB 50116-2013 第6.2.4条 Code for design of automatic fire alarm systems

System Equipment消防工程

GB 50116-2013 第6.2.4条

| Point-type heat fire detector: when installed on the ceiling of an internal corridor less than 3 m wide, the installation spacing shall not exceed 10 m; the distance from the detector to the end wall shall not be greater than half of the installation spacing.