GB 50116-2013 第6.2.2条
| Point-type photoelectric smoke fire detector: When installed on the ceiling of an interior corridor less than 3 m wide, it should be centered; the installation spacing should not exceed 15 m; the distance from the detector to the end wall should not exceed half of the installation spacing.