GB 50116-2013 第3.3.3条 Code for Design of Automatic Fire Alarm Systems

System Design消防工程

GB 50116-2013 第3.3.3条

| Detector installation spacing: smoke detector installation spacing shall not exceed 15 m; heat detector installation spacing shall not exceed 10 m.