GB 50116-2013 第3.1.1条 Code for Design of Automatic Fire Alarm Systems

System design消防工程

GB 50116-2013 第3.1.1条

| Selection of automatic fire alarm system type: A local alarm system is suitable when only alarm is required without linkage; a centralized alarm system is suitable when linkage is required and there is no dedicated control room; a control center alarm system is suitable when two or more fire control rooms are provided (e.g., large hotel complexes).