GB 50116-2013 第3.2.6条 Code for Design of Automatic Fire Alarm Systems

Cabling消防工程

GB 50116-2013 第3.2.6条

| When cables are laid in conduits or cable trays, their total cross-sectional area shall not exceed 40% of the conduit's internal cross-sectional area or 60% of the cable tray's cross-sectional area.