GB 50116-2013 第3.2.5条 Code for Design of Automatic Fire Alarm Systems

Cabling消防工程

GB 50116-2013 第3.2.5条

| When the power supply lines and transmission lines of the automatic fire alarm system are installed outdoors, they shall be buried underground, and the burial depth shall not be less than 0.7m.