GB 50116-2013 第3.2.2条 Code for Design of Automatic Fire Alarm Systems

Cabling消防工程

GB 50116-2013 第3.2.2条

| When fire control, communication and alarm circuits are concealed, they shall be run in metal conduits or flame-retardant rigid plastic conduits and embedded within non-combustible structural layers, with a protective cover thickness of not less than 30 mm; when surface-mounted, they shall be run in metal conduits or metal trunking with fire protection measures taken.