GB 50116-2013 第4.5.1条 Code for Design of Automatic Fire Alarm Systems

Fire alarm linkage control消防工程

GB 50116-2013 第4.5.1条

| Smoke control system: The alarm signal from two independent fire detectors in the fire compartment where the pressurization air supply outlet is located, or from one detector and one manual alarm call point, shall serve as the linkage trigger signal for opening the air supply outlet and starting the pressurization supply fan.