GB 50116-2013 第3.8.3条 Code for Design of Automatic Fire Alarm Systems

Fire detector消防工程

GB 50116-2013 第3.8.3条

| In public areas of hotel buildings such as corridors and elevator lobbies, the spacing between point-type smoke detectors shall not exceed 15 m, and the distance to the end wall shall not exceed 7.5 m (a special clause applicable to hotel buildings).