GB 50116-2013 第3.4.1条
| The horizontal distance from the detector to walls and beam edges shall not be less than 0.5 m; the horizontal distance to the edge of an air-conditioning supply outlet shall not be less than 1.5 m, and the detector should preferably be installed close to the return air inlet.