GB 50116-2013 第3.2.1条 Code for design of automatic fire alarm systems

Fire detector消防工程

GB 50116-2013 第3.2.1条

| The protection area of a point-type heat detector shall not exceed 30㎡, and the protection radius shall not exceed 4.4m; when the installation height exceeds 8m, heat detectors shall be selected.

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.